RA-N

The Danfoss RA-N radiator valves with pre-setting feature are used in two-pipe water based heating systems to ensure optimum distribution of the water in a heating system. Optimal hydronic balancing can provide significant energy savings and improved comfort experience. The pre-setting ring allows precise adjustment of the flow in seven steps - no tools needed. Just give a slight pull and turn the ring with your hand. RA-N valves are available for normal and low flows and for reversed flow.

Kv value at setting 5 [m³/h]
Kv value at setting 6 [m³/h]
Differential pressure range [bar] [Max]
Presetting
Kv value at setting 1 [m³/h]
Kv measuring range
Kv value at setting 4 [m³/h]
Kv value at setting 7 [m³/h]
Test pressure [bar]
Kv value at setting 3 [m³/h]
Connection size out
Kv value at setting N [m³/h]
Working pressure [bar] [Max]
Flow temperature [°C] [Max]
Kv value at setting 2 [m³/h]
Dimension standard
Dimension
Connection size in
RA-N 25 VALVE BODY DIN 013G0038
0.350 m3/h
0.460 m3/h
0.60 bar
Yes
0.100 m3/h
0.10 - 1.0
0.260 m3/h
0.730 m3/h
16 bar
0.170 m3/h
R 1
1.040 m3/h
10 bar
120 °C
0.150 m3/h
D
25
Rp 1
RA-N 20 VALVE BODY DIN 013G0036
0.350 m3/h
0.460 m3/h
0.60 bar
Yes
0.100 m3/h
0.10 - 1.0
0.260 m3/h
0.730 m3/h
16 bar
0.170 m3/h
R 3/4
1.040 m3/h
10 bar
120 °C
0.150 m3/h
D
20
Rp 3/4
RA-N 15 S "D" 013G0034
0.300 m3/h
0.400 m3/h
0.60 bar
Yes
0.040 m3/h
0.04 - 0.7
0.200 m3/h
0.510 m3/h
16 bar
0.120 m3/h
R 1/2
0.730 m3/h
10 bar
120 °C
0.080 m3/h
D
15
Rp 1/2
RA-N 10 S "D" 013G0032
0.250 m3/h
0.330 m3/h
0.60 bar
Yes
0.040 m3/h
0.04 - 0.5
0.190 m3/h
0.380 m3/h
16 bar
0.120 m3/h
R 3/8
0.560 m3/h
10 bar
120 °C
0.080 m3/h
D
10
Rp 3/8